Multi-function Control Card with voltage outputfor VESDA VLF

Product no.: 6073-Tarjeta-multifunc-VESDAVLF-salida-tension

In stock
can be shipped within 1 - 5 days

796.52 €
590.02
You save 26 %

Price incl. VAT, plus delivery



Available delivery methods: Standard delivery Spain Portugal, International postal service (EU), CANARY ISLANDS T2LF Merchandise without dispatch declaration., National sent Professionals, Shipping worldwide, Pick up in physical store., Shipping PG, Shipment for boluminosa terrestrial packages with delivery in Spain and Portugal

Multi-function Control Card for VESDA VLF-250/ VLF-500 with voltage output

 

The Xtralis VESDA VLF MCC (Multi-function Control Card) is an interface card for the range of Xtralis VESDA VLF smoke detectors. An MCC expands the range of input and output communications a VLF can perform.

Installing a VLF MCC into a VLF detector provides a cost-effective solution for customers who need enhanced connectivity, fault detection and monitoring,and annunciation of alarms and faults.

The principal benefits include:

Improved FACP connectivity

The VLF is fitted with two (2) alarm relays in its standard form. With an extra two (2) relays, the Multi-function Control Card allows reporting of all four (4) alarm levels on dry relay outputs.

Enhanced annunciation

An MPO (Monitored 24 V Powered Output) is available on the VIC-030 version of the card. The MPO provides power to devices such as sirens or strobes, and monitors the line integrity.

Enhanced control and fault detection

With a VLF MCC installed, a VLF has two (2) General Purpose Inputs (GPIs), allowing, for example, one GPI to report on loss of mains power and the other GPI to be used as a reset input.

The VIC-030 version of the card has a self-configuring GPI, depending on the jumper selection for MPO/Relay3. 

• If MPO is selected, activation of the GPI will disable the MPO. 

• If Relay3 is selected, the GPI will be set to External Fault (e.g. for mains power supply monitoring)

 

Features

VIC-030

• Provides two (2) additional relays

• Provides an extra General Purpose Input

(GPI) with line monitoring

• Quick and simple to install

• Out-of-the-box operation, with minimal configuration required for extra features

• Diagnostic LEDs give visual indication of the card’s status

• Fully compatible with Xtralis VESDA VLF smoke detectors

· Selection between 3rd relay or 24 V Monitored Powered Output (MPO)

 

Specifications

Dimensions Length x Width x Height 110 mm (41/3”) x 70 mm (2 3/4”) x 20 mm (13/16”) Weight 0.08 kg (0.176 lb)

Terminals 0.2 - 2.5 mm2 (30-12 AWG)

 

Electrical Ratings 

Power consumption 1 W from the detector at 24 VDC (less than 42 mA)

Relay outputs 2 A at 30 VDC

MPO input power supply 24 VDC (VIC-030 only)

MPO input current 100 mA more than MPO output load (VIC-030 only)

MPO output current 1 A (maximum) (VIC-030 only)

End of line resistor (MPO & GPI) 2.7K Ohm

 

Operating Conditions

Detector ambient temperature 0 to 40°C (32 to 104°F)

Humidity 5% to 95% (non-condensing)

Detector Compatibility

Supports VLF-250 and VLF-500

Product Warranty 2 years

 

Input/Output Assignments

VIC-030

Output for Relay 1: ALERT (follows latching configuration of VLF ALERT status)

Output for Relay 2: FIRE-2 (follows latching configuration of VLF FIRE-2 status)

MPO: ALERT (unless disabled) (follows latching configuration of VLF ALERT status)

Jumper configuration

J9

J10

GPI for MPO: Disable MPO

MPO status is driven as follows:

- EOL > MPO enabled

- Short > MPO disabled*

- O/C > MPO enabled and Fault # 111/IFF8

Output for Relay 3: DISABLED or STANDBY (follows VLF DISABLED or STANDBY status)

Jumper configuration

J9

J10

GPI for Relay 3: FAULT

GPI reports status on following conditions:

- EOL > No fault

- Short >Fault # 115/IFF6

- O/C > Fault # 111/IFF8

* The MPO is disabled if there is a short on the GPI.

 

 

VIC-030, Vesda, multifunction card, VESDA card, accessories VESDA, accessories VesdaVLF 

Additional product information

Wholesale price 361.20 €

Accessories

Product Note Status Price
Cable fire Halogen-free shielded Cable fire Halogen-free shielded
118.54 € * Notify on availability
Fire Cable 2 x 1.5 twisted Fire Cable 2 x 1.5 twisted
182.32 € *
Fire Cable 2 x 1.5 shielded Fire Cable 2 x 1.5 shielded
70.60 € *
Battery of 12V/ Consumption of 7 A Battery of 12V/ Consumption of 7 A
13.96 € *

Product data sheet

Battery of 12V/ Consumption of 5 A Battery of 12V/ Consumption of 5 A
9.63 € *

Product data sheet

Battery 12V / 4.2 Ah Battery 12V / 4.2 Ah
13.92 € *
*
Prices incl. VAT, plus delivery
Display accessory details

We also recommend

*
Prices incl. VAT, plus delivery

Browse this category: Fire Alarm Accessories