Rate of rise heat detector. Base not included.
The fire detector provides reliable early warning of a Fire condition upon reaching a rate of rise of the temperature or fixedtemperature threshold in the protected premises.
The fire detector is suitable for premises with normal ambient temperature, without possible sudden changes.
Technical data
Supply voltage: (10-30)VDC
Duty mode current: 55 μA
Fire condition current:
- with base type 8000 or 8000D
(8-25) mA (not included)
- with base type 8000R, 8000DR
(18-55) mA (not included)
Terminals: For wires with cross section (0.8-2.5)mm2
Degree of protection: IP 43
Operation temperature: Minus 10oC to 55oC
Relative humidity: (93±3) % at 40oC
Sensitivity: In accordance with EN54-5, class A2R
Mounting: Using bases of series 8000 (not included)
Dimensions: Ø100, h 47 mm
Casing material: ABS plastics, white
Weight: 0.100 kg
Protected area: Circle with diameter 10m, h 8m
Detector, velocimetric detector, detectors thermovelocimetric, thermovelocimetric conventional detector, conventional detectors thermovelocimetric, conventional detector, thermovelocimetric UniPOS, UniPOS, CFDTV101, FD8020