Multi-function Control Card for VESDA VLF-250/ VLF-500 with voltage output
The Xtralis VESDA VLF MCC (Multi-function Control Card) is an interface card for the range of Xtralis VESDA VLF smoke detectors. An MCC expands the range of input and output communications a VLF can perform.
Installing a VLF MCC into a VLF detector provides a cost-effective solution for customers who need enhanced connectivity, fault detection and monitoring,and annunciation of alarms and faults.
The principal benefits include:
Improved FACP connectivity
The VLF is fitted with two (2) alarm relays in its standard form. With an extra two (2) relays, the Multi-function Control Card allows reporting of all four (4) alarm levels on dry relay outputs.
Enhanced annunciation
An MPO (Monitored 24 V Powered Output) is available on the VIC-030 version of the card. The MPO provides power to devices such as sirens or strobes, and monitors the line integrity.
Enhanced control and fault detection
With a VLF MCC installed, a VLF has two (2) General Purpose Inputs (GPIs), allowing, for example, one GPI to report on loss of mains power and the other GPI to be used as a reset input.
The VIC-030 version of the card has a self-configuring GPI, depending on the jumper selection for MPO/Relay3.
• If MPO is selected, activation of the GPI will disable the MPO.
• If Relay3 is selected, the GPI will be set to External Fault (e.g. for mains power supply monitoring)
Features
VIC-030
• Provides two (2) additional relays
• Provides an extra General Purpose Input
(GPI) with line monitoring
• Quick and simple to install
• Out-of-the-box operation, with minimal configuration required for extra features
• Diagnostic LEDs give visual indication of the card’s status
• Fully compatible with Xtralis VESDA VLF smoke detectors
· Selection between 3rd relay or 24 V Monitored Powered Output (MPO)
Specifications
Dimensions Length x Width x Height 110 mm (41/3”) x 70 mm (2 3/4”) x 20 mm (13/16”) Weight 0.08 kg (0.176 lb)
Terminals 0.2 - 2.5 mm2 (30-12 AWG)
Electrical Ratings
Power consumption 1 W from the detector at 24 VDC (less than 42 mA)
Relay outputs 2 A at 30 VDC
MPO input power supply 24 VDC (VIC-030 only)
MPO input current 100 mA more than MPO output load (VIC-030 only)
MPO output current 1 A (maximum) (VIC-030 only)
End of line resistor (MPO & GPI) 2.7K Ohm
Operating Conditions
Detector ambient temperature 0 to 40°C (32 to 104°F)
Humidity 5% to 95% (non-condensing)
Detector Compatibility
Supports VLF-250 and VLF-500
Product Warranty 2 years
Input/Output Assignments
VIC-030
Output for Relay 1: ALERT (follows latching configuration of VLF ALERT status)
Output for Relay 2: FIRE-2 (follows latching configuration of VLF FIRE-2 status)
MPO: ALERT (unless disabled) (follows latching configuration of VLF ALERT status)
Jumper configuration
J9
J10
GPI for MPO: Disable MPO
MPO status is driven as follows:
- EOL > MPO enabled
- Short > MPO disabled*
- O/C > MPO enabled and Fault # 111/IFF8
Output for Relay 3: DISABLED or STANDBY (follows VLF DISABLED or STANDBY status)
Jumper configuration
J9
J10
GPI for Relay 3: FAULT
GPI reports status on following conditions:
- EOL > No fault
- Short >Fault # 115/IFF6
- O/C > Fault # 111/IFF8
* The MPO is disabled if there is a short on the GPI.
VIC-030, Vesda, multifunction card, VESDA card, accessories VESDA, accessories VesdaVLF